Type 1, Type 2 and Type 3 devices do different jobs. Here is how to stage them across an Indian LT distribution.
Three stages, three duties
Type 1 SPDs at the main incomer handle partial lightning current (Iimp, 10/350 µs). Type 2 devices at sub-distribution clamp the residual to equipment-tolerable levels. Type 3 devices sit close to sensitive loads to control the last few hundred volts of let-through.
Coordination rules that get missed
Maintain the manufacturer's minimum cable length or decoupling inductance between stages, keep connecting leads under 0.5 m total, and bond every SPD earth to the same equipotential bar as the LPS down conductors. An uncoordinated SPD set can be worse than none at all.
Send your drawings. Get a compliant system design back.
Share roof plans, structure height and soil data — our team returns a risk assessment summary, air termination or earthing layout, bill of materials and a fixed-price proposal.
- Risk assessment to IS/IEC 62305-2
- IEC 62561 type-tested ARK Make components